Excellent price !!!
Easy set-up - directly fit to IEC & NEMA contactors
Free from noise, accurate operation
AC/DC wide control voltage range



Model
PG50-2EP
PG30/50-UCR
PG01/06/30-2EP
PG06/30/50-2ES
 
TYPE
Direct fit to Contactor
Terminal fit to Contactor
Direct fit to Contactor
Terminal fit to Contactor
Ampere Range (A)
5 ~ 50 (A)
3 ~ 32(A)
10 ~ 50(A)
PG01
PG06
PG30
PG06
PG30
PG50
0.1~1.4
0.5~6.5
3~32
0.5~6.5
3~32
10~50
Time Characteristic
Definite Time / (*Option-Inverse)
Definite Time
Definite Time /
(*Option-Inverse)
Definite Time /
(*Option-Inverse)
Motor (KW)
220~240V
1.5 ~ 7.5(KW)
-
~0.05
0.12~0.75
0.55~3.7
Covers All range of motor
380~440V
3.7 ~ 11(KW)
-
~0.15
0.25~1.5
1.5~7.5
PG06 + CT (all range)
Protection
Overcurren
O
Under Current
O
O
Phase Unbalance
-
-
-
-
Phase Loss
Phase Reverse
-
-
-
-
Time Setting
(Second)
O-Time (Sec)
0~30 (sec)
0~30 (sec)
0~30 (sec) 0~30 (sec)
Reset Time
Manual Reset
(*Auto Reset -180Sec.Optional)
Manual Reset
Manual Reset
(*Auto Reset -180Sec.Optional)
Manual Reset
(*Auto Reset -180Sec.Optional)
Control Voltage
Voltage
L1/L2 95~260V(* 380/440V /DC-Optional)
Frequency
50/60Hz
Output Relay
Contact
-A type
1-SPDT (1c)
Running
Normally de-energised contact (COM/95 - NC/96 - NO/98)
Capacity
5A/250V- Resistive Load
Insulation
Min 50M at 500V DC
Surge
7 kv(6 times per 1 Minute)
Environment
Running
-25 ~ 70
Storage
-50~ 80
Humidity
45~85 RH
Operation Display
LED GreenPower On / RedOverload
Mounting
Screw
Screw & DIN RAIL
(35mm)
Screw
Screw & DIN RAIL(35mm)




Thank you for using PG OPR Electronic Motor Protection Relay.

1. Check point before using
    Please check the model feature and any damage to parts during the delivery.

2. Operation Time Setting

    (1) Adjust operation time control knob considering the motor start time.
    (2) 0бн30 second

3. Trip Current Setting

    Set the current control knob at the maximum range. Then run the motor
    Turn the control knob anticlockwise until overcurrent display lamp ON (O. L),
    then turn the knob clockwise until the lamp OFF. This point is 103бн 105% of real current.

4. Test

    (1) If push the test button after power on, the relay display lamp is ON and power lamp OFF,
     then the relay will be tripped.
    (2) When tripped, push the Reset button. Overcurrent display lamp will be off and power lamp
     will be on and the relay will be returned to initial condition.










1
Current Range
PG -
01
0.1 ~ 1.4 A
Over 35A:
06 TYPE + External C/T (Current Transformer)
06
0.5 ~ 6.5 A
30
3 ~ 32 A
50
10~ 50A
2
Connect to MC
2EP
Direct Connection to MC w/Pin
Terminal contact
2ES
Terminal Contact or Separate use
3
Control Voltage
110
24 -130V AC/DC
* AC/DC 24V - Optional
220
100 - 220V AC
440
380 - 440V AC
4
Output Relay
No letter
1 - SPDT ( 1c ) Normal Close/Open
B
2 - SPST ( 1a 1b ) Normal Close/Open
5
Time Characteristic
No letter
Definite Time Characteristic
T
Inverse Time Characteristic
6
Reset type
No letter
Manual Reset type
A